Phase Failure Relay (PFR) GC1100
GC1100 phase failure relays protect three phase lines, transformers, motors, generators, and another three phase loads against phase unbalance, phase loss, and phase reversal.
GC1100 phase failure relays protect three phase lines, transformers, motors, generators, and another three phase loads against phase unbalance, phase loss, and phase reversal.
The output relay energizes and the green BALANCE LED lights when a balanced input with the proper phase sequence is sensed. The output relay de-energizes and the BALANCE LED goes out when a fault condition is detected.
One external potentiometer control - ASYMMETRY (%) - is provided. The potentiometer adjusts percentage of unbalanced voltage at which the relay trips. A factory presented hysteresis provides enough and sufficient time delay to prevent relay tripping on voltage transients. The units are self-powered.
Specification
| Nominal voltage | 380Vac |
| Frequency | 50 Hz |
| Set point range | adjustable 5% … 25% of Nominal voltage |
| Relay type | SPDT – Contact rating 5A (cosφ = 1), 250 Vac |
| Burden | 5VA / 4W (max) |
| Operating temperature | 0°C … +50°C |
| Storage temperature | -10°C … +70°C |
| Relative humidity | 95% (non condensing) |
| Weight | 324 gr |
| Mounting | DIN rail 35 x 7.5 mm |